EasyManua.ls Logo

Selec TC544C

Selec TC544C
6 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Voltage dips and
interruptions
Dips : 0% residual voltage /
1 cycle (Criteria B), 40% residual voltage /
10 cycles 50Hz / 12 cycles 60Hz
(Criteria C)70% residual voltage /
25 cycles50Hz / 30 cycles 60Hz
(Criteria C)
Interruptions : 0% residual voltage /
250 cycles 50Hz / 300 cycles 60Hz
(Criteria C)
IEC 61000-4-11
Level III
Conducted emission
Radiated emission
Electrical fast transient
CISPR-11
CISPR-11
IEC 61000-4-4
Compliance
Applicable EMI / EMC standards
Product standard : IEC 61326-1
Category
Standards compliance
ESD immunity
Level III
Surge immunity
+/- 2 kV common mode,
+/- 1 kV differential mode
Radiated susceptibility
Level III, 80 to 1000MHz
Level II, 1.4GHz to 2GHz
Level I, 2GHz to 2.7GHz
Conducted susceptibility
Level II
IEC 61000-4-2
IEC 61000-4-5
IEC 61000-4-3
IEC 61000-4-6
TC544C
Temperature Controller
Supply voltage
Output 2Output 1
Certification
Product code
RELAY
TC544C
RELAY SSR 90 to 270V AC / DC
Ordering Information
Accessories (Optional)
Standard SELEC accessories that can be used with this product.
Mounting accessories (Supplied with units)
Input sensor ranges
Download
Device
Independent Downloader module (IDM)

Related product manuals