Fan controls
0 – fan is on, no defrosting
1 – fan is on depending on the evaporator detector temperature
Setting – fan switching on
fan on if: evaporator temp.< fan setting – alarm hist. (FSt - AHS)
fan off: evaporator temp. > fan setting (FSt)
Fan switching off if compressor is on.
0 – no switching off
1 – switching off
Low temp. alarm – deviation from setting
ALo=0-alarm off
High temp. alarm – deviation from setting
AHI=0-alarm off
2
1
2
2
2
1
1
1
2
2
1
+15
0
1
2
5
5
60
6
1
2
-30
01
0
1
0
0
0
0
0
6
5
0
1
5
20
20
120
20
+20
001
O
C
O
C
O
C
O
C
min
min
Fan during defrosting and dripping
0 – switching on
1 – switching off
Temp. alarm delay
Fan standstill time after dripping phase
19
20
21
22
23
24
25
26
27
28
28
FFn
FSt
Fco
FdF
FSd
AHS
ALo
AHI
AdL
rL2
rL3
Temperature and fan alarm histeresis
High temp. alarm on = setting + AHI
High temp. alarm off = setting + AHI - AHS
Low temp. alarm on = setting - ALo
Low temp. alarm off = setting - ALo + AHS
Relay (output) 2 - function
0 - inactive (off)
1 - fan
2 - lighting -'PRG' button
3 - alarm HI – transmitter on during 'HI' message
4 - alarm LO – transmitter on during 'LO' message
5 - LO and HI alarms - transmitter on during 'LO' and 'HI' messages
6 - defrosting
only ERT-10-2-221C and ERT-10-2-222C
Relay (output) 3 - function
0 - inactive (off)
1 - fan
2 - lighting -'PRG' button
3 - alarm HI – transmitter on during 'HI' message
4 - alarm LO – transmitter on during 'LO' message
5 - LO and HI alarms - transmitter on during 'LO' and 'HI' messages
only ERT-10-3-321C
U.M. Type
Default.
Min Max
Nr
Code
Parameter
14
15
16
17
18
Defrosting parameters
Time between defrosting
End of defrosting temperature
Drip time – compressor and fan switching on delay
Value displayed on the screen during defrosting
0 – actual temperature
1 – commencement of defrosting temperature – return to normal indications
after reaching the temperature before defrosting or reaching the set temperature
Max. defrosting time
For modes 2 and3–itisdefrosting time.
121 – unlimited defrosting time
dCL
dEt
dLt
dAd
ddL
O
C
min
min
1
1
1
1
2001
3020
8
60
+7
2
0
2
40
+35
121
hours.
Evaporator fan parameters
Alarm parameters
Other settings
4
Parameter types:
1 - Parameters available without service password.
2 - Parameters requiring service password (all parameters)