Manual – Fieldbus Interface INTERBUS UFI11A
List of Errors
91 System error None Please check the red SYS-FLT LED
on the UFI11A. If this LED is on,
then one or more stations on the
SBus could not be addressed within
the timeout delay. If the red SYS-
FLT LED is flashing, then the
UFI11A itself is in error status. In
this instance, error 91 alone was
transmitted to the control via the
fieldbus.
Check the voltage supply and the
SBus cabling, check the SBus ter-
minating resistors. Check the con-
figuration if the UFI11A was
configured with the PC. Switch the
UFI11A off and on again. Check
the error code using the diagnostic
interface if the error remains, and
take the action described in this
table.
97 Copy data SBus communi-
cation stopped
An error occurred while the data
record was being copied. The data
are not consistent.
Carry out the "delivery condition"
factory setting, perform a reset and
then try to copy the data again.
Error
code
Name Response Cause Action