14 Service
14.1 Diagnostic procedures
The diagnostics procedures described in the following section demonstrate the fault
analysis methods for the following problems:
• Inverter does not operate on EtherCAT
®
.
• Inverter cannot be controlled using the EtherCAT
®
master.
Additional information on parameterization can be found in the MOVIMOT
®
inverter
operating instructions.
Please also refer to the information on voltage supply in chapter "Installation instruc-
tions for fieldbus interfaces, field distributors"(→235).
Step 1: Check the connection between the inverter and EtherCAT
®
Are the bus plugs properly plugged in the master and EtherCAT
®
interface?
NO →
[A]
YES
↓
What are the "L/A" LEDs on the EtherCAT
®
interface doing?
OFF →
[A]
ON
↓
Is the EtherCAT
®
interface physically connected to the EtherCAT
®
properly? Check the EtherCAT
®
connection at X11 IN (EtherCAT
®
incoming) and X12 OUT (EtherCAT
®
outgoing).
NO →
[A]
YES
↓
Continue with 2: What is the "RUN" LED doing?
[A] Check the bus cabling.
Step 2: What is the "RUN" LED doing?
"RUN" LED =
OFF
Has the master switched the slave to INIT
state?
YES →
NO →
[A]
[B]
"RUN" LED
flashes green
Slave is in PRE-OPERATIONAL state. → [C]
"RUN" LED
lights up green
1x
Slave is in SAFE-OPERATIONAL state. → [C]
"RUN" LED
lights up green
Slave is in OPERATIONAL state. → [C]
[A] Startup the bus in the master.
[B] EtherCAT
®
interface is defective.
[C] Continue with 3: What is the "ERR" LED do-
ing?