15
Technical data
Technical data for field distributors
Manual – EtherCAT
®
Interfaces, Field Distributors
122
15.4 Technical data for field distributors
15.4.1 MF../Z.3. field distributors
MF../Z.3.
Supply voltages V
line
AC 3 x 380V -10% – AC 500V +10%
AC 3 x 200V -10% – AC 240V +10%
Line frequency f
line
50–60Hz
Max. permitted total cur-
rent X1
(X1 terminal)
I
max
32A (according to UL max. 30A)
Max. permitted total current
X21
(X21 terminals)
32A
Max. permitted total cur-
rent X20
(X20 terminals)
12A
Ambient temperature -25°C–60°C
Storage temperature -25°C–85°C
Degree of protection IP65 (fieldbus interface and motor connection cable attached and
fastened, all plug connections sealed)
Interface PROFIBUS, PROFINET IO, EtherNet/IP™, EtherCAT
®
, DeviceNet™
Permitted motor cable
length
max. 30m (with SEW‑EURODRIVE hybrid cable, type B)
for cross section reduction compared to the supply system cable
Note the line fusing.
Mass Approx. 1.3kg
25809148/EN – 01/2019