6
Electrical installation
Installation planning taking EMC aspects into account
Manual – EtherCAT
®
Interfaces, Field Distributors
33
6 Electrical installation
6.1 Installation planning taking EMC aspects into account
INFORMATION
This drive system is not designed for operation on a public low voltage supply system
that supplies residential areas.
MOVIMOT
®
can cause EMC interference within the permitted limit range according to
EN61800-3. In this case, it is recommended for the operator to take suitable meas-
ures.
For detailed information on EMC-compliant installation, refer to the SEW publication
Drive Engineering – Practical Implementation, "Electromagnetic Compatibility in Drive
Engineering".
Successful installation of decentralized drives depends on selecting the correct
cables, providing correct grounding and a functioning equipotential bonding.
Always adhere to the relevant standards.
Observe the notes in the following chapters in particular.
6.1.1 Equipotential bonding
Low-impedance and HF-capable equipotential bonding must be provided independent
of the PE connection (see also VDE0113 or VDE0100 part540).
Establish a connection over a wide surface area between the field distributor and the
system (untreated, unpainted, uncoated mounting surface).
Do not use the cable shields of data lines for equipotential bonding.
17948651787
[1] Conductive connection over a large area between field distributor and mounting
plate
[2] PE conductor in the supply system cable
[3] Connection second PE conductor
If you install a highly flexible PE conductor with a large cross section (e.g.
6mm
2
), this PE conductor also fulfills the function of an HF-capable equipotential
bonding in terms of EMC.
25809148/EN – 01/2019