6
Electrical installation
Installation planning taking EMC aspects into account
Manual – EtherCAT
®
Interfaces, Field Distributors
33
6 Electrical installation
6.1 Installation planning taking EMC aspects into account
INFORMATION
This drive system is not designed for operation on a public low voltage supply system
that supplies residential areas.
MOVIMOT
®
can cause EMC interference within the permitted limit range according to
EN61800-3. In this case, it is recommended for the operator to take suitable meas-
ures.
For detailed information on EMC-compliant installation, refer to the SEW publication
Drive Engineering Practical Implementation, "Electromagnetic Compatibility in Drive
Engineering".
Successful installation of decentralized drives depends on selecting the correct
cables, providing correct grounding and a functioning equipotential bonding.
Always adhere to the relevant standards.
Observe the notes in the following chapters in particular.
6.1.1 Equipotential bonding
Low-impedance and HF-capable equipotential bonding must be provided independent
of the PE connection (see also VDE0113 or VDE0100 part540).
Establish a connection over a wide surface area between the field distributor and the
system (untreated, unpainted, uncoated mounting surface).
Do not use the cable shields of data lines for equipotential bonding.
[2]
[1]
[3]
17948651787
[1] Conductive connection over a large area between field distributor and mounting
plate
[2] PE conductor in the supply system cable
[3] Connection second PE conductor
If you install a highly flexible PE conductor with a large cross section (e.g.
6mm
2
), this PE conductor also fulfills the function of an HF-capable equipotential
bonding in terms of EMC.
25809148/EN – 01/2019