• Connect the shield to the housing of both units using EMC cable glands. Also ob-
serve the further notes regarding the selection of the cable glands.
• Generally provide the GND reference potential.
• Twist the conductors as shown in the following figure.
6.2 Installation instructions for fieldbus interfaces, field distributors
6.2.1 Connecting supply system leads
• The nominal voltage and frequency of the MOVIMOT
®
inverter must correspond to
the data for the power supply system.
• Dimension the cable cross section according to the input current I
line
for rated
power (see MOVIMOT
®
operating instructions, "Technical data" chapter).
• Install fuses at the beginning of the power supply cables behind the supply bus
junction.
The following fuses are permitted:
– Fuses in utilization category gG
– Power circuit breakers with characteristic B or C
– Motor circuit breaker
Size the fuses according to the cable cross section.
• SEW‑EURODRIVE recommends using earth-leakage monitors with pulse-code
measurement in voltage supply systems with a non-grounded star point (IT sys-
tems). Using such devices prevents the earth-leakage monitor mis-tripping due to
the ground capacitance of the inverter.