6
Electrical installation
Installation instructions for fieldbus interfaces, field distributors
Manual – EtherCAT
®
Interfaces, Field Distributors
36
6.2.2 Notes on PE connection
WARNING
Electric shock due to faulty ground connection or faulty equipotential bonding.
Severe, fatal injuries
The permitted tightening torque for the retaining screws is 2.0 – 2.4Nm.
Make sure to install the ground connection and equipotential bonding correctly.
Prohibited assembly Recommendation:
Assembly with forked cable lug
Permitted for all cross sections
Assembly with solid connecting
wire
Permitted for cross section
up to max. 2.5mm
2
[1]
M5
2.5 mm²
M5
[1] Forked cable lug suitable for M5 PE screws
Earth-leakage currents of 3.5 mA can occur during normal operation. To meet the
requirements of EN61800-5-1, observe the following notes:
The protective earth (PE) connection must meet the requirements for plants with
high earth-leakage currents.
This usually means
installing a PE connection cable with a minimum cross section of 10mm
2
or installing a second PE connection cable via separate terminals that must not
be smaller than the cable cross section of the supply system cable.
25809148/EN – 01/2019