6
Electrical installation
Connection of EtherCAT®
Manual – EtherCAT
®
Interfaces, Field Distributors
58
Only use shielded cables and connection elements that meet the requirements of cat-
egory 5, class D according to IEC11801 edition 2.0.
The following measures ensure the best possible EMC properties:
Manually tighten the mounting screws on the connectors, modules
and equipotential bonding conductors.
Use only connectors with a metal housing or a metalized housing.
Route signal and bus cables in separate cable ducts. Do not route them parallel to
power cables (motor leads).
Use metallic, grounded cable racks in industrial environments.
Route the signal cable and the corresponding equipotential bonding close to each
other using the shortest possible route.
Avoid using plug connectors to extend bus cables.
Route the bus cables closely along existing grounding surfaces.
6.7.2 Bus termination
Bus termination (e.g. with bus terminating resistors) is not necessary. If no slave is
connected to an EtherCAT
®
device, it recognizes this immediately.