6
Electrical installation
Hybrid cable connection
Manual – EtherCAT
®
Interfaces, Field Distributors
62
6.10 Hybrid cable connection
6.10.1 Hybrid cable between MFZ.3. or MFZ.6. field distributor and MOVIMOT
®
The following figure shows the hybrid cable for connecting the MOVIMOT
®
drive part
number (01867253).
9007200401506827
The following table shows the terminal assignment of the hybrid cable in the
MOVIMOT
®
connection box:
Terminal assignment
MOVIMOT
®
terminal Wire color/hybrid cable designation
L1 Black/L1
L2 Black/L2
L3 Black/L3
24V Red/24V
⍊ White/0V
RS+ Orange/RS+
RS- Green/RS-
PE terminal Green/yellow + shield end
Note the enabled direction of rotation
Check to see if requested direction of rotation has been enabled.
Both directions of rotation
are enabled.
Drive is inhibited or is being
brought to a standstill.
Only CCW operation is en-
abled.
Setpoint specifications for
CW rotation result in stop-
ping of drive.
Only CW operation is en-
abled.
Pre-selected setpoints for
CCW rotation result in stop-
ping of the drive.
25809148/EN – 01/2019