11
Supplementary field distributor startup information
MOVIMOT® inverter integrated in field distributor
Manual – EtherCAT
®
Interfaces, Field Distributors
90
S1 5
Motor protec-
tion
6
Motor power
rating
7
PWM fre-
quency
8
No-load
damping
Meaning
ON Off Motor one
size smaller
Variable
(16, 8, 4kHz)
On
OFF On Adjusted 4kHz Off
Setpoint poten-
tiometer f1
10
0
100
2
75
25
50
10
f
1
[1]
1
2
3
4
5 6
7
8
9
f1
Hz
9007200441723659
[1] Factory setting
All other settings are identical to the settings for a MOVIMOT
®
drive with integrated in-
verter. See MOVIMOT
®
operating instructions.
11.4.2 Additional functions for MOVIMOT
®
integrated in the field distributor
The following additional functions are available when MOVIMOT
®
is integrated in the
Z.7., Z.8. or Z.9. field distributor (to a limited extent). A detailed description of the addi-
tional functions can be found in the MOVIMOT
®
operating instructions.
Additional function Restriction
1 MOVIMOT
®
with increased ramp times –
2 MOVIMOT
®
with adjustable current limiting
(fault if limit is exceeded)
–
3 MOVIMOT
®
with adjustable current limiting
(switchable using terminal f1/f2)
Not available
4 MOVIMOT
®
with bus configuration Not available
5 MOVIMOT
®
with motor protection in Z.7., Z.8.
or Z.9. field distributor
–
6 MOVIMOT
®
with maximum 8 kHz PWM fre-
quency
–
7 MOVIMOT
®
with rapid start/stop The mechanical brake can
only be controlled by
MOVIMOT
®
. It is not possible
to control the brake using
the relay output.
8 MOVIMOT
®
with minimum frequency 0Hz –
10 MOVIMOT
®
with minimum frequency 0 Hz and
reduced torque at low frequencies
–
11 Monitoring of line phase failure deactivated –
25809148/EN – 01/2019