12.2 MFE status word
The following figure shows the assignment of the status word of the MFE fieldbus in-
terface:
2-byte MFE status
15 14 12 1113 10 9 7 68 5 4 2 13 0
Reserved = "0"
7: MFE system error
8: Overload actuator voltage DO0
9: Overload actuator voltage DO1
12: Overload sensor voltage I
Reserved = "0"
Reserved = "0"
Byte nByte n+1
MFE status
MFE
Bus
master
28240664459
The following table shows the diagnostics information of the MFE fieldbus interface set
up for evaluation in the higher-level PLC application. The signals are transferred to the
controller via parameters and via the process data channel.
The logical communication status "0" signals the status "OK" for each signal. There-
fore, the asynchronously running start-up sequences of the PLC and the device do not
output any false diagnostic messages upon start-up of the system (bus start-up with
useful data= 0).
MFE status bit Diagnostic name via bus Function and coding
0, 1, 2 Reserved –
7 MFE system error MFE system error
1 = MFE system error present.
0=OK
See parameter index 8310 for more in-
formation.
8 Overload actuator voltage DO0 Short circuit/overload of the actuator sup-
ply for output DO0
1 = Short circuit/overload DO0
0=OK
9 Overload actuator voltage DO1 Short circuit/overload of the actuator sup-
ply for output DO1
1 = Short circuit/overload DO1
0=OK
10, 12 Reserved –
25809148/EN – 01/2019