Chapter 6 inverter of function parameter
No. Code
Describing LED/OLED
Keyboard display
Setting range
Change
P06.18 Filtering time of AI2 input
0.00s~10.00s
◇
P06.19
Gain for simulated input 1
K1
0.00~300.00
◇
P06.20
Gain for simulated input 2
K2
0.00~300.00
◇
Function of AI2 is similar to the setting method of AI1.
Analog AI2 can support the input with 0~10V or 0~20mA; when AI2 chooses the input with 0~
20mA , voltage corresponding with 20mA is 10V.
There are 5 (below) multifunctional input terminals of the number and 2 input terminals of analog in the
standard unit of PT200 series AC frequency vector inverter.
6-2-8.P07group human-computer interface group
No. Code
Describing LED/OLED
Keyboard display
Setting range
Change
P07.00
User password
0~65535
◇
When the setting is any number except 0, the password protection takes effect. 00000: remove the
user password value set before and make the protection function of password effective; and resetting to
factory can also remove the password.
After the user password is set and effective, the user can’t enter into the parameter menu if the user
password is wrong; the user can view and change the parameters only by inputting correct user password.
Please remember the user password set carefully.
Exit the editing state of function code, then the password protection will take effect in one minute;
press to enter into the editing state of function code after the password takes effect, it will show
“0.0.0.0.0.”; the operator must input the password correctly, or the operator can’t enter.
P07.01
OLED shows language
choice
0: Chinese
1:English
◇
0:Chinese
1:ENGLISH
The above function is only effective for outer keyboard of OLED. It is used for choose languages of
liquid crystal display.
P07.02
Copy of function
parameter
0: No operation
1: Function parameter of this
machine is delivered to OLED
keyboard
2: Download function
parameter of OLED keyboard
onto this machine
Notice: the parameter
automatically returns to 0 after
1-2 operations have been
finished
□