Peripheral devices
INVERTER INTRODUCTION 16
3.5 Installation and wiring
3.5.1 Transportation
Take the pedestal when carrying and don’t only take the cover or any part of the inverter, otherwise it may drop down.
3.5.2 Storage
Keep this product in the packaging before installation and when not in use. To change the frequency that meets the
manufacturer’s warranty and maintenance conditions, please pay attention to the following regarding storage:
1. Must be placed in dry and without dirt place.
2. The environment temperature for storage position must range from -20℃ to +65℃.
3. The relative humidity for storage position must range from 0% to 95%, and no condensation.
4. Avoid storing in the environment which contains corrosion gas or liquid.
5. It had better be packed properly and kept on shelf or table.
Note: 1. Even if the humidity meets the standard requirements, icing and condensation can also occur when the
temperature changes rapidly. And the place should avoid.
2. Don't place it on the ground, and it should be placed on appropriate shelf. If in the bad surroundings, the
desiccant should be placed in the packaging bag.
3. If the custody period is more than 3 months, the ambient temperature should not be higher than 30℃. It is to
consider that the character will easily degrade in high temperature when the electrolytic capacitors are
deposited without electricity.
4. If the inverter is installed in device or control board when not in use (especially in construction site or the
humid and dusty place), the inverter should be removed and put in suitable environment according with the
above storage conditions.
5. If the electrolytic capacitors are long-term no electricity, the character will degrade. Do not place it in the state
of no electricity for more than one year.
3.5.3 Installation notice
Before installation, please confirm whether meet the conditions listed in the table below:
-10 ~ +50℃ (non-freezing)
90%Rh 以下(non-condensing).
Indoor, no corrosive gas, no flammable gas, no flammable powder.
Altitude below 2000 meters, when altitude is above 1,000 m, derate the rated current 2% per 100 m.
Vibration below 5.9m/s
2
(0.6G).
Please ensure vertical arrangement to keep the cooling effect:
(a) Vertical arrangement (b) Horizontal arrangement (c) Level arrangement