Troubleshooting
100 © SICK AG • Subject to change without notice • 8021823/126P/2018-12-17
12 Troubleshooting
The following table describes possible interferences and measures for
removal.
Contact the manufacturer for interferences that cannot be removed based
onthefollowingdescription.Youcanndyourlocaloceonthereverse.
General interferences, warnings
and errors
Thedistancemeasuringdevicedierentiatesbetweengeneral
interferences, warnings and errors. General interferences are not
displayed. When a warning is pending, the LED PWRashesorange.A
measurement value is output When an error is pending, the LED PWR
ashesred.Themeasurementvalue"0"isoutput.
12.1 LED status indicators
Display Possible causes Troubleshooting
The display shows the value
"0000".
The measuring device's light spot does not
hitthereector.
Correct alignment between measuring
deviceandreector.
The obstacle is in the light path. Remove obstacle from the light path.
Distance between distance measuring
deviceandreectorexceedsthemaximum
scanning range indicated in the technical
data. → see page 106, chapter 14.3.
• Decrease the distance between the
distance measuring device and the
reector.
• Select a distance measuring device with a
larger maximum scanning range.
LED PWR is not lit. Display is
lit.
Measuring device defective. Send in device for repair.
LED PWRashesorange. A warning is pending.
→ For possible causes and their removal,
see page 101, chapter 12.2.
LED PWRashesred. An error is pending.
→ For possible causes and their removal,
see page 101, chapter 12.3.
LEDs BF and SFo. PROFINET connection OK.
Device boot-up.
–
LED BFashingandLEDSFo. Ethernet connection OK.
PROFINET boot-up.
Devicenotconguredorincorrectlycong-
ured.
–
–
• Conguredeviceand/orcheckcongura-
tion.
LED BF on. LED SFo. No Ethernet cable connected. • Connect Ethernet cable.
LED BFoorashing.LEDSF
ashing.
PROFINETstationashingtestactive. –
Table 58: LED status display