Troubleshooting
102 © SICK AG • Subject to change without notice • 8021823/126P/2018-12-17
Display Meaning / possible causes Troubleshooting
eLevel Current damping value is below the warning
threshold. The warning threshold depends
on the distance between measuring device
andreector.For recommended damping
values, see page 31, Table 6.
Clean external lens surfaces like the
reectorandthelens.
Decrease the distance between the
measuringdeviceandthereector.
Use a distance measuring device with a
higher range.
see page 109, chapter 14.10.
eTemp The internal devicetemperature is outside of
the permissible range.
For the permissible ambient temperature,
see page 108, chapter 14.8.
Check ambience temperature, improve
ventilation if applicable.
Shield against radiation heat, e.g. shade
the measuring device in case of direct
solar irradiation.
Use device with heating at low ambient
temperatures.
Use cooling housings for high ambient
temperatures.
Table 60: Error messages
12.4 PROFINET IO error messages
Display Meaning / possible causes Troubleshooting
Device error Hardware Check supply voltage and wiring.
For electrical connection, see page 35,
chapter 7.
Switchsupplyvoltageonando.
Send in measuring device for repair.
The internal devicetemperature is outside of
the permissible range.
For the permissible ambient temperature,
see page 108, chapter 14.8.
Wait for warm-up phase of the measuring
device. Let the measuring device cool
down.
Check ambience temperature, improve
ventilation if applicable.
Shield against radiation heat, e.g. shade
the measuring device in case of direct
solar irradiation.
Use device with heating at low ambient
temperatures.
Use cooling housings for high ambient
temperatures.
Measuring error Light path between measuring device and
reectorinterrupted.
Keep replacement device ready.
Current damping value is below the recom-
mended damping value. The recommended
damping value depends on the distance
betweenmeasuringdeviceandreector.
For recommended damping values, see page
31, Table 6.
Clean external lens surfaces like the
reectorandthelens
Lensorreectorcontaminated. Clean external lens surfaces like the
reectorandthelens
Movement too fast. Check maximum movement speed.