PROFINET IO-interface
88 © SICK AG • Subject to change without notice • 8021823/126P/2018-12-17
Input values
Rel. Adr. Description
0 Device temperature [°C]
Type
Prex-applied8bitdigitinacomplementoftwo
1 Device-specicvalueforthesignalreceptionquality.
Type
Prex-applied16bitdigitinacomplementoftwo
3 Operating hours in 10 hour units.
Type
Prex-applied16bitdigitinacomplementoftwo
10.3.10 Module 20: "MFx"
Type Congurationmodule,noinputandoutputdata
Description This module determines the ratio between the switchable input and output
MF1.
Module parameter "MFx"
Name Description
MFx Activate or deactivate switching inputs or switching output.
Value range
enable
disable
Standard value
Disable
Module parameter "MF1"
Name Description
MF1 Function Select function for input and output MF1.
Value range
[Output] Distance Threshold: Output switches when the
distance from module parameter "[MF1 Distance]
Threshold" was undercut.
[Output] Speed Threshold: Output switches when the speed
from module parameter "[MF1 Distance] Speed" was
exceeded. The direction is determined in the module
parameter "[MF1 Speed] mode".
[Output] Service: The output switches when at least one of
the service bits activated was set.
[Input]LaserO:Themeasurementlaserisdeactivatedvia
the input.
[Input] Preset Static: "Preset Static" function is activated via
the input.
Standard value
[Output] Distance Threshold: