LEDs on the fieldbus module
Table 119: LEDs on the fieldbus module
LED Meaning
POWER
O
Supply voltage on
o
Supply voltage off or too low
LINK/ACT
O
Ethernet connection present
o
No Ethernet connection
Ö 1Hz
Data is being received or sent
STATUS
9)
OGreen
No error, data is being exchanged between the master and slave.
Ö Green
***TBD***
ORed
Bus error, faulty connection, data exchange is not possible.
Ö Red
Incorrect parameters, data exchange is not possible. The MLG-2 is not
configured or has been configured incorrectly (e.g., incorrect address
setting).
Ö Red/green
System error, data can be exchanged with the MLG-2. Diagnostic infor‐
mation is available.
LEDs on control panel of the MLG-2
Table 120: LEDs on control panel of the MLG-2
LED Meaning
Alignment
O
Light path blocked (at least one beam blocked)
o
No object in the light path
Ö 3Hz
Contamination warning or alignment aid active and alignment poor
Ö 1Hz
Teach-in or password recovery through physical access active
10.4 Advanced diagnostics on the MLG-2
The supplied SOPAS ET software contains advanced diagnostics options. These options
allow you to further isolate the problem if the error situation is unclear or if there are
availability issues. You can find detailed information:
In the Status field (in the bottom left of the main screen)
In the system boundaries display (minimum detectable object for the current
configuration, minimum presence time, reproducibility, response time)
9)
The STATUS LED follows the respective fieldbus specification
10 TROUBLESHOOTING
154
O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK
Subject to change without notice