5.2 Sender connections
In the case of the MLG-2, the sender and receiver synchronize with each other electron‐
ically. This means that cabling is required between the sender and fieldbus module.
You must connect the Sync_A signal on the sender to Sync_A on the fieldbus module,
and Sync_B on the sender to Sync_B on the fieldbus module. You will find the Sync_A
and Sync_D signals at the POWER connection of the fieldbus module.
Sender connection: M12/5-pin, A-coded
Table 27: Pin assignment, sender connection
Male connector Pin Signal Meaning Color
1 L+ 24V supply voltage Brown
2 Sync_A Synchronization White
3 M GND supply voltage Blue
4 Test_In Test input Black
5 Sync_B Synchronization Gray
ELECTRICAL INSTALLATION 5
8018748.1Q3I/2024-12-18 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet