Figure 71: Beam numbering
This might be a good idea, for example, if you mount the MLG-2 with the connections
facing upward, but still want to measure height classification from the bottom.
NOTE
Beam numbering has consequences for the beam functions FBB, FBM, LBB, LBM, CBB,
CBM, RLC, and on the beam status.
7.4.3.6 Factory settings
Table 97: Factory settings
Index Access Data type Description
75h R/W BOOL This parameter is used to reset the MLG-2 to
its factory settings.
0 = no reset
1 = reset to factory settings
You have the option to reset the MLG-2 to the factory settings.
If you reset to factory settings, you will lose all data that has already been configured.
NOTE
The factory settings are restored as soon as 1 is written.
The MLG-2 will be reset too. Therefore, the control reports, where necessary, an
error that the MLG-2 is no longer available.
The following applies after resetting to factory settings:
°
No process data such as beam functions or beam status is output.
°
The alignment aid is active.
°
A teach-in is required. All functions become available again only after a
successful teach-in process.
7 THE MLG-2 ON THE PROFIBUS NETWORK
88
O P E R A T I N G I N S T R U C T I O N S | MLG-2 ProNet 8018748.1Q3I/2024-12-18 | SICK