EasyManua.ls Logo

Siemens 38-3AH3 38 kV - Page 64

Siemens 38-3AH3 38 kV
68 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix
Measured parameter Units Circuit breaker type
1
38-3AH3-31 38-3AH3-40
General Nominal voltage class kV
38.0 38.0
Rated
values
Rated
voltage
Maximum design voltage (V)
2
kV rms
38.0 38.0
Voltage range factor (K)
3
----
1.0 1.0
Insulation
levels
Withstand
voltage levels
Power-frequency kV rms
80 80
Lightning-impulse (BIL) kV peak
150 150
Rated
current
Continuous
4
A rms
1,200, 2,000,
3,000FC
1,200, 2,000,
3,000FC
Short-circuit (at rated maximum design voltage)
(I)
5, 6
kA rms sym
31.5 40
Interrupting time
7
Cycles/ms
5/83 5/83
Permissible tripping delay (Y) Sec
2 2
Related
required
capabilities
Current Rated maximum design voltage (V) divided by K =
(V/K)
kA rms
38.0 38.0
Maximum symmetrical (sym) interrupting (K x I) kA rms sym
31.5 40
%dc component %
47 47
Short-time current (K x I) (three-seconds) kA rms sym
31.5 40
Closing and
latching
(momentary)
Asymmetrical (1.55 x I) kA rms
49 62
Peak (2.6 x I) kA peak
82 104
Footnotes:
1
"xxxx" in type designation refers to the
continuous current rating 1,200, 2,000 or
3,000 A, as appropriate. The 3,000 A fan-
cooled rating is achieved using fan cooling as
indicated in Footnote 4.
2
Maximum design voltage the circuit breaker is
designed for and the upper limit for operation.
3
K is listed for informational purposes only. For
circuit breakers rated on a "constant kA basis,"
the voltage range factor is 1.0.
4
3000FC indicates fan cooling is included in the
switchgear structure for this rating. 3000 A
rating is not available in outdoor equipment.
5
All values apply to polyphase and line-to-line
faults.
6
Standard duty cycle is O - 0.3s - CO - 3 min. -
CO.
7
Three-cycle (50 ms) interrupting is optionally
available.
These ratings are in accordance with:
ANSI/IEEE C37.04-1999 Standard Rating
Structure for AC High-Voltage Circuit
Breakers
ANSI/IEEE C37.06-2009 AC High-
Voltage Circuit Breakers Rated on a
Symmetrical Current Basis - Preferred
Ratings and Related Required
Capabilities
ANSI/IEEE C37.09-1999 Standard Test
Procedure for AC High-Voltage Circuit
Breakers Rated on a Symmetrical
Current Basis
ANSI/IEEE C37.010-1999 Application
Guide for AC High-Voltage Circuit
Breakers Rated on a Symmetrical
Current Basis.
Table 12: Type 38-3AH3 vacuum circuit breaker ratings (new "constant kA" ratings basis)