51
ANSI/IEEE C37.06 control voltages
Close
coil
Trip coil
Spring charging motor
Nominal
Range
Run
(Average)
1
Inrush
(Peak)
Charging
Close Trip A
1
A
1
A A Seconds
24 Vdc 19-28 14-28 5.7 15/---- ---- ---- ----
48 Vdc 36-56 28-56 11.4 11.4/30
3
8 25 10
125 Vdc 100-140 70-140 2.1 4.8/7.4
3
4 18 10
250 Vdc 200-280 140-280 2.1 4.2/9.6
3
2 10 10
120 Vac 104-127 104-127 2.0 ----
2
6 ---- 10
240 Vac 208-254 208-254 2.0 ----
2
3 ---- 10
Table 11: Type 3AH vacuum circuit breaker ratings (new "constant kA" ratings basis)
These ratings are in
accordance with:
ANSI/IEEE C37.04-1999
Standard Rating Structure
for AC High-Voltage Circuit
Breakers
ANSI/IEEE C37.06-2009 AC
High-Voltage Circuit
Breakers Rated on a
Symmetrical Current Basis -
Preferred Ratings and
Related Required
Capabilities for Voltages
Above 1,000 Volts
ANSI/IEEE C37.09-1999
Standard Test Procedure
for AC High-Voltage Circuit
Breakers Rated on a
Symmetrical Current Basis
ANSI/IEEE C37.010-1999
Application Guide for AC
High-Voltage Circuit
Breakers Rated on a
Symmetrical Current Basis.
Footnotes:
1.
Maximum design voltage for
which the circuit breaker is
designed and the upper limit for
operation.
2.
K is listed for information
purposes only. For circuit
breakers rated on a "constant kA"
ratings basis, the voltage range
factor is 1.0.
3.
All values apply to polyphase and
line-to-line faults.
4.
Standard duty cycle is O - 0.3 s -
CO - 3 min. - CO.
5.
Standard rating interrupting time
is five-cycles (83 ms). Optional
rated interrupting time of three-
cycles (50 ms) is available
(except with 24 Vdc tripping).
6.
150 kV BIL is for drawout
applications. 200 kV BIL is for
type SDV6 with appropriate
construction.
7.
Continuous current capability
may be increased by the use of
forced-cooling (fan-cooling) in
the switchgear together with
increased bus bar capacity.
Circuit breaker
type
Maximum
design
voltage (V)
1
Voltage
range
factor
(K)
2
Withstand voltage
levels
Continuous
current
7
Short-circuit
(I)
3,4
kV rms
Power
frequency
kV rms
Lightning
impulse
(BIL)
kV crest
A rms kA rms sym
5-3AH-31.5 4.76 1.0 19 60 1,200, 2,000 31.5
5-3AH-40 4.76 1.0 19 60
1,200, 2,000,
3,000
40
5-3AH-50 4.76 1.0 19 60
1,200, 2,000,
3,000
50
5-3AH-63 4.76 1.0 19 60
1,200, 2,000,
3,000
63
7-3AH-40 8.25 1.0 36 95
1,200, 2,000,
3,000
40
15-3AH-20 15.0 1.0 36 95 1,200, 2,000 20
15-3AH-25 15.0 1.0 36 95 1,200, 2,000 25
15-3AH-31.5 15.0 1.0 36 95
1,200, 2,000,
3,000
31.5
15-3AH-40 15.0 1.0 36 95
1,200, 2,000,
3,000
40
15-3AH-50 15.0 1.0 36 95
1,200, 2,000,
3,000
50
15-3AH-63 15.0 1.0 36 95
1,200, 2,000,
3,000
63
15.5-3AH-20 15.5 1.0 50 110 1,200, 2,000 20
15.5-3AH-25 15.5 1.0 50 110 1,200, 2,000 25
15.5-3AH-31.5 15.5 1.0 50 110 1,200, 2,000 31.5
15.5-3AH-40 15.5 1.0 50 110
1,200, 2,000,
3,000
40
27-3AH-20 27.6 1.0 60 150 1,200, 2,000 20
27-3AH-25 27.6 1.0 60 150 1,200, 2,000 25
38-3AH-20 38.0 1.0 80 150/200
6
1,200, 2,000 20
38-3AH-25 38.0 1.0 80 150/200
6
1,200, 2,000 25
38-3AH-31.5 38.0 1.0 80 150/200
6
1,200, 2,000,
3,000
31.5
38-3AH-40 38.0 1.0 80 150/200
6
1,200, 2,000,
3,000
40