Maintenance schedule
No. Work to be done Operating and
auxiliary materials
Frequency
Bemerkungen
*) mechanical operating
cycles
annually
every 10 000*)
every 30 000*)
after 60 000*)
1. Vacuum circuit-breaker
1.1 Clean insulating parts and outer
parts
Warm water, house-
hold cleaners
x Note 1)
1.2 Grease all bearing points and
sliding surfaces as per Fig. 70 and
Fig. 69. Perform 3 to 5 mechanical
test switching operations after
greasing
Isoflex Topas L32
Shell Tellus Oil32
x See Fig. 70 und Fig. 69
Note 2), 3), 6)
1.3 Check all electrical operating
materials in the drive for correct
functioning and replacing, just in
case
x
1.4 Check line connections for tight seat x
1.5 Check all screw connections and
locking elements for tight fit and
check for completeness
x
2. Pole assembly
2.1 Exchange vacuum interrupters x Possibly depending on the
electrical operating cycle
number as per “Interrupter
service live”,
Note 4)
x Only for 3AH4305-7/8,
3AH4306-7/8, Maintenance
at the Siemens plant
2.2 Exchange spring guide and
insulating operating rod
x Note 4)
2.3 Angle lever x Only for 3AH4305-6/7/8 and
3AH4306-6/7/8,
Note 4)