EasyManua.ls Logo

Siemens 3MT7 Series - User Manual

Siemens 3MT7 Series
20 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
EN
EN
ES
TR
PT
Power Contactor
Güç Kontaktörü
Contactor de potencia
3MT7...
Operating Instructions
Instructivo
İşletme Kılavuzu
Instruções de operação
Last update : 01 Oct 2022.
Technical Assistance :
E-mail - technical-assistance@siemens.com
Internet - https://support.industry.siemens.com
Contator de potência
TR PT
ES
Hazardous voltage. Will cause death or serious injury.
Turn off and lock out all power supplying this device before working on this device.
Tensión peligrosa. Puede causar la muerte o lesiones graves.
Desconectar la alimentación eléctrica antes de trabajar en el equipo.
Tehlikeli gerilim. Ölüm tehlikesi veya ağır yaralanma tehlikesi.
Çalışmalara başlamadan önce, sistemin ve cihazın gerilim beslemesini kapatınız.
Desligue e bloqueie a energia antes de manusear o dispositivo
Tensão perigosa. Causará morte ou ferimentos graves.
DANGER
PELIGRO
TEHLİKE
PERIGO
EN
ES
TR
PT
Question and Answer IconNeed help?

Do you have a question about the Siemens 3MT7 Series and is the answer not in the manual?

Overview

This document provides an overview of the Siemens 3MT7 series power contactors, including their assembly, various accessories, and technical specifications.

Function Description

The Siemens 3MT7 series are power contactors designed for switching electrical loads. They are available in various sizes (Size 0 to Size 4) to accommodate different current ratings and applications. The contactors can be used individually or assembled into reversing contactor configurations with appropriate interlock modules. Various accessories, such as auxiliary switches, surge suppressors, and pneumatic timers, can be added to enhance their functionality.

Important Technical Specifications

General:

  • Product Series: 3MT7... (Power Contactor)
  • Sizes:
    • Size 0: 3MT7006-0. to 3MT7012-0.
    • Size 1: 3MT7018-1. to 3MT7022-1.
    • Size 2: 3MT7025-2. to 3MT7040-2.
    • Size 3: 3MT7040-3. to 3MT7065-3.
    • Size 4: 3MT7070-4. to 3MT7095-4.
  • Mounting Position: Can be mounted at any angle within 360 degrees, with specific recommendations for 22.5° tilt.

Terminal Data (L1, L2, L3, T1, T2, T3):

  • Size 0 (3MT7006-0. to 3MT7012-0.):
    • Screw Type: M3.5
    • Torque: 1.2 Nm
    • Wire Cross-Section: 1 x (1...4) mm², 2 x (1...4) mm²
    • Stripping Length (D): 10 mm
  • Size 1 (3MT7018-1. to 3MT7022-1.):
    • Screw Type: M3.5
    • Torque: 1.7 Nm
    • Wire Cross-Section: 1 x (1.5...6) mm², 2 x (1.5...6) mm²
    • Stripping Length (D): 10 mm
  • Size 2 (3MT7025-2. to 3MT7040-2.):
    • Screw Type: M4
    • Torque: 1.85 Nm
    • Wire Cross-Section: 1 x (1.5...10) mm², 2 x (1.5...6) mm²
    • Stripping Length (D): 15 mm
  • Size 3 (3MT7040-3. to 3MT7065-3.):
    • Screw Type: M8
    • Torque: 5.0 Nm
    • Wire Cross-Section: 1 x (2.5...25) mm², 2 x (2.5...16) mm²
    • Stripping Length (D): 22 mm
  • Size 4 (3MT7070-4. to 3MT7095-4.):
    • Screw Type: M10
    • Torque: 9.0 Nm
    • Wire Cross-Section: 1 x (4...50) mm², 2 x (4...35) mm²
    • Stripping Length (D): 22 mm

Terminal Data (NO/NC - Auxiliary Contacts):

  • Sizes 0, 1, 3 & 4:
    • Screw Type: M3.5
    • Torque: 1.2 Nm
    • Wire Cross-Section: 1 x (1...4) mm², 2 x (1...4) mm²
    • Stripping Length (D): 8.5 mm
  • Size 2:
    • Screw Type: M4
    • Torque: 1.2 Nm
    • Wire Cross-Section: 1 x (1...4) mm², 2 x (1...4) mm²
    • Stripping Length (D): 8.5 mm

Terminal Data (A1/A2 - Coil Terminals):

  • All Sizes:
    • Screw Type: M3.5
    • Torque: 1.2 Nm
    • Wire Cross-Section: 1 x (1...4) mm², 2 x (1...4) mm²
    • Stripping Length (D): 8.5 mm

Terminal Data (Pneumatic Timer / Auxiliary Switches / Surge Suppressor):

  • All Sizes:
    • Screw Type: M3.5
    • Torque: 1.2 Nm
    • Wire Cross-Section: 1 x (1...4) mm², 2 x (1...4) mm²
    • Stripping Length (D): 8.5 mm

Dimensional Drawings (all dimensions in mm):

  • Size 0: 82 (Length) x 45 (Width) x 74 (Height)
  • Size 1: 86.5 (Length) x 45 (Width) x 74 (Height)
  • Size 2: 95 (Length) x 56 (Width) x 83 (Height)
  • Size 3: 112.6 (Length) x 74.5 (Width) x 127.4 (Height)
  • Size 4: 121.3 (Length) x 84.5 (Width) x 127.4 (Height)

Usage Features

Contactor Assembly:

  • Basic Mounting: Contactors are typically mounted onto a DIN rail. For Sizes 0, 1, and 2, a simple "CLICK" mechanism secures the contactor. For Sizes 3 and 4, a similar "CLICK" mechanism is used, but the overall dimensions are larger.
  • Reversing Contactor Assembly:
    • Sizes 0, 1, 2: An interlock module (e.g., 3MT7900-1XM01) is inserted between two contactors from the back. The module slides in and is secured by a "PUSH" mechanism.
    • Sizes 3, 4: An interlock module (e.g., 3MT7900-1XM03) is inserted between two contactors. The assembly is then mounted onto a DIN rail with a "CLICK" action. Screws (3x M4, 2 Nm) are used to secure the assembly to a mounting plate. For Sizes 3 and 4, an additional screw (1.2 Nm) is used to secure the interlock module.
    • Mechanical Interlock (3MT7900-1XE01/02/03): These modules provide mechanical interlocking for reversing applications. They are inserted between two contactors, and a "PUSH" mechanism secures them. For Sizes 3 and 4, the interlock module is mounted on a DIN rail with a "CLICK" action, and then secured with a screw (1.2 Nm).

Auxiliary Switches:

  • Front Auxiliary Switches (3MH79..0CT10): These modules are attached to the front of the contactor with a "CLICK" mechanism.
  • Lateral Auxiliary Switches (3MH79..-0CL10): These modules are attached to the side of the contactor with a "CLICK" mechanism. Different models are available for Sizes 0, 1, 2 and Sizes 3, 4.

Surge Suppressor Assembly (3MT79001S..):

  • Surge suppressors are inserted into designated slots (A1/A2) on the contactor. For Sizes 0, 1, 2, a screw (1.2 Nm) secures the suppressor. For Sizes 3, 4, the suppressor is inserted and secured with a screw (1.2 Nm).

Pneumatic Timer Assembly (3MT79000P..):

  • Pneumatic timers (e.g., 3MT79000PN10 for ON DELAY, 3MT79000PF10 for OFF DELAY) are mounted on the front of the contactor with a "CLICK" mechanism. They have adjustable time settings.

Maintenance Features

Replacing of Spare Coil (3MT79000L..):

  • Sizes 0, 1, 2:
    1. Unscrew the coil retaining screw (1 Nm).
    2. Remove the top housing and pull out the coil.
    3. Insert the new coil.
    4. Reassemble the top housing and secure with the screw (1 Nm).
  • Sizes 3, 4:
    1. Unscrew the coil retaining screw (4 Nm).
    2. Remove the top housing and pull out the coil.
    3. Insert the new coil.
    4. Reassemble the top housing and secure with the screw (4 Nm).

Replacing of Spare Top Housing (3MT79...-OHA.. to 3MT79..-2HA for Sizes 0, 1, 2; 3MT79...-3HA.. to 3MT79..-4HA for Sizes 3, 4):

  • Sizes 0, 1, 2:
    1. Unscrew the top housing retaining screw (1 Nm).
    2. Remove the old top housing.
    3. Place the new top housing.
    4. Secure with the screw (1 Nm).
  • Sizes 3, 4:
    1. Unscrew the top housing retaining screw (4 Nm).
    2. Remove the old top housing.
    3. Place the new top housing.
    4. Secure with the screw (4 Nm).

Safety Information:

  • DANGER: Hazardous voltage. Will cause death or serious injury. Always turn off and lock out all power supplying the device before working on it.
  • PELIGRO (Spanish): Tensión peligrosa. Puede causar la muerte o lesiones graves. Desconectar la alimentación eléctrica antes de trabajar en el equipo.
  • TEHLİKE (Turkish): Tehlikeli gerilim. Ölüm tehlikesi veya ağır yaralanma tehlikesi. Çalışmalara başlamadan önce, sistemin ve cihazın gerilim beslemesini kapatınız.
  • PERIGO (Portuguese): Tensão perigosa. Causará morte ou ferimentos graves. Desligue e bloqueie a energia antes de manusear o dispositivo.

This document is subject to change without prior notice and should be stored for future reference.

Siemens 3MT7 Series Specifications

General IconGeneral
BrandSiemens
Model3MT7 Series
CategoryIndustrial Equipment
LanguageEnglish

Related product manuals