PROFIBUS DP communication module
9.12 Data sets (BS)
3RW44 soft starters
194 Manual, 03/2017, NEB535219502000/RS-AB/008
Data set 81 - Reading the basic settings of data set 131
Data set 81 corresponds in structure and content to data set 131. Data set 81 supplies the
default values for all parameters of data set 131.
Data set 82 - Reading the basic settings of data set 132
Data set 82 corresponds in structure and content to data set 132. Data set 82 supplies the
default values for all parameters of data set 132.
Data set 83 - Reading the basic settings of data set 133
Data set 83 corresponds in structure and content to data set 133. Data set 83 supplies the
default values for all parameters of data set 133.
Data set 92 - Reading device diagnostics
Table 9- 23 Data set 92 - Reading device diagnostics
301 0
0
Ready (automatic) - Device is ready for operation via
host (e.g. PLC), alarm bit is updated
continually.
306 0
1
Motor CW - Contact block 1 is switched on,
alarm bit is updated continually.
307 0
2
Motor CCW - Contact block 2 is switched on,
alarm bit is updated continually.
309 0
3
Contact block overload F5, F24 e.g. power semiconductor too hot,
causing motor to trip.
Alarm bit is automatically deleted
when the cause of the fault has
been removed and acknowledged
308 0
4
Contact block defective F9 e.g. contactor is fusion-
welded/jammed or power
semiconductor has fused.
Alarm bit can only be deleted by
switching the supply voltage on and
off once the cause of the error has
310 0
5
Emergency start active - Alarm bit is deleted when
emergency start is deactivated.