PROFIBUS DP communication module
9.12 Data sets (BS)
3RW44 soft starters
214 Manual, 03/2017, NEB535219502000/RS-AB/008
Data set 160 - Reading/writing communication parameters
This data set is meant only for devices with direct access to the fieldbus (e.g. PROFIBUS
DP) for assignment of communication parameters.
Table 9- 33 Data set 160 - Reading/writing communication parameters
200 0 Coordination 0x20 Writing via C1 channel (PLC)
0x30 Writing via C2 channel (PC)
0x40 Writing 0x40 via device interface (PC)
211 5 Baud rate 12 000 kBd [0]
6 000 kBd [1]
3 000 kBd [2]
1 500 kBd [3]
500 kBd [4]
187.5 kBd [5]
93.75 kBd [6]
45.45 kBd [7]
19.2 kBd [8]
9.6 kBd [9]
Not used [10..14]
Automatic baud rate
Note
3RW44 soft starters signal the current baud rate while reading. During writing, the value
entered is ignored, as the baud rate is always automatically detected by the soft starter.