Directional Time-Overcurrent Protection, Ground
Setting Values for the Function Direction Determination
Method for direction determination Zero sequence
Negative sequence
Minimum V0 or V2 threshold 0.150 V to 20.000 V 0.001 V
Rotation angle of the reference voltage -180° to 180°
Forward range 0° to 180°
Setting Values for All Stage Types
Direction mode Forward
Reverse
Method of measurement Fundamental component
RMS value
Threshold value 1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A
5 A @ 50 and 100 Irated 0.15 A to 175.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.030 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.15 A to 8.000 A Increments of 0.001 A
Setting Values for Stage Type Definite Time-Overcurrent Protection
Dropout ratio
0.90 to 0.99 Increments of 0.01
Operate delay 0.00 s to 60.00 s Increments of 0.01 s
Dropout delay 0.00 s to 60.00 s Increments of 0.01 s
Setting Values for Stage Type Inverse Time-Overcurrent Protection (IEC/ANSI)
Type of characteristic curve
Characteristic curves according to IEC and ANSI
Dropout Disk emulation
Instantaneous
Time multiplier 0.00 to 15.00 Increments of 0.01
Minimum time of the curve 0.00 to 1.00 s Increments of 0.01 s
Additional time delay 0.00 to 60.00 s Increments of 0.01 s
Dropout Values for Stage Type Inverse Time-Overcurrent Protection (IEC/ANSI)
Disk emulation
Approx. 0.90 * threshold value
Instantaneous Approx. 1.05 * threshold value
Approx. 0.95 * pickup value
Characteristic Curves for Stage Type Inverse Time-Overcurrent Protection (IEC/ANSI)
Standard Characteristic Curves According to IEC
Normal inverse: type A
Refer to the respective picture of the technical data for the non-
dir-OC-ground function 11.9.2 Stage with Inverse-Time Charac-
teristic Curve
Very inverse: type B
Extremely inverse: type C
Long-time inverse
Standard Characteristic Curves According to ANSI/IEEE
11.11
Technical Data
11.11 Directional Time-Overcurrent Protection, Ground