Figure 6-34 Additional Parameters for Switching Authorities in the Parameters of a Switching Device
When activating the parameter Swi.dev. related sw.auth., an individual switching authority as well as
an individual switching mode for this switching device are configured. Additional signals are displayed in the
Control function block of the corresponding switching device.
[sc_extended parameters sw authority sw device, 1, en_US]
Figure 6-35 Expanded Parameters for the Switching Authority in the Switching Device
[sc_switching auth sw mode changeable, 1, en_US]
Figure 6-36 Individually Modifiable Switching Authority and Switching Mode for Switching Devices
The new input signals that are displayed allow you to set the individual switching authority and switching
mode for the switching devices. For this switching device, these inputs overwrite the central switching
Control Functions
6.3 Control Functionality