[sc_FBadjcomm, 1, en_US]
Figure 6-83 Extract from the DIGSI Library
Delete the stages of the synchronization function that are not used.
Routing the Voltage Transformers to the Measuring Points
NOTE
Ensure that the transformer connections available in the specific application are routed to the correct meas-
uring point!
You can find the routing in the DIGSI 5 project tree under Function-group connections → Connect meas-
uring points to function group.
•
Route the system-side transformer connections in the FG Circuit breaker to the input V Sync 1.
•
Route the generator-side transformer connections in the FG Circuit breaker to the input V Sync 2.
The following figures show possible connection variants for the voltage transformers:
[dw_dim_two_3ph-voltage-trans, 1, en_US]
Figure 6-84 Connection of Two 3-Phase Voltage Transformers
Control Functions
6.4 Synchronization Function
396 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017