[sc_FBadjcomm, 1, en_US]
Figure 6-83 Extract from the DIGSI Library
Delete the stages of the synchronization function that are not used.
Routing the Voltage Transformers to the Measuring Points
i
i
NOTE
Ensure that the transformer connections available in the specific application are routed to the correct meas-
uring point!
You can find the routing in the DIGSI 5 project tree under Function-group connectionsConnect meas-
uring points to function group.
Route the system-side transformer connections in the FG Circuit breaker to the input V Sync 1.
Route the generator-side transformer connections in the FG Circuit breaker to the input V Sync 2.
The following figures show possible connection variants for the voltage transformers:
[dw_dim_two_3ph-voltage-trans, 1, en_US]
Figure 6-84 Connection of Two 3-Phase Voltage Transformers
Control Functions
6.4 Synchronization Function
396 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017