EasyManua.ls Logo

Siemens 6SR41 series - Page 148

Siemens 6SR41 series
202 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Application and Operation
6.14 Cell Bypass
Product User Manual
146 Operating Instructions, Version AE 12/2009, A5E01454341C
0RGXOH'ULYHDIWHU
%\SDVVRI0RGXOHV
LQ3KDVH$RQO\DQG
$
GMXVWPHQWRISKDVH
$
QJOHV
RIWKH0RGXOHV
DUHLQXVHRIIXOO
YROWDJHLVDYDLODEOH
$
%
&
9$&
9%$
9&%
$
$
$
%
%
%
%
%
&
&
&
&
&
r
r
r
Figure 6-20 Drive Output Re-Balanced by Adjusting Phase Angles (Neutral Shift)
The same neutral-shift approach can be applied to more extreme situations, as is illustrated
by Figure "Drive Output after Loss of 3 Cells" and Figure "Drive Output after Loss of 5 Cells"
2. Figure "Drive Output after Loss of 3 Cells" shows a drive which originally had five cells per
phase, or a total of 15 cells. All five cells remain in phase A, but one cell has faulted in phase
B and two cells have faulted in phase C. Without neutral-shift, all phases would need to be
reduced to match the cell count of phase C to maintain balanced motor voltages. One
functional cell would be bypassed in phase B, and two functional cells would be bypassed in
phase A. Only 60% of the original cells would remain in use, and only 60% of the original
voltage would be available.
However, with the neutral-shift approach shown in Figure "Drive Output after Loss of 3
Cells", only the faulted cells are bypassed. The phase angles of the cell voltages have been
adjusted so that phase A is displaced from phase B by 96.9° and from phase C by 113.1°,
instead of the normal 120°. The star point of the cells no longer coincides with the neutral of
the motor voltages, but the motor voltage is still balanced. The neutral-shift keeps 80% of the
original cells in use, and 70% of the original voltage is available.
0RGXOH'ULYHDIWHU
%\SDVVRI0RGXOHLQ
3KDVH%DQG0RGXOHVLQ
3KDVH&
RIWKH0RGXOHVDUHLQ
XVHRIIXOOYROWDJHLV
DYDLODEOH
$
$
$
$
$
&
&
&
%
%
%
%
9$&
r r
9%&
$
%
&
9&%
Figure 6-21 Drive Output after Loss of 3 Cells
As another example, Figure "Drive Output after Loss of 5 Cells" shows the same 15-cell
drive. All five cells remain in phase A, but two cells have faulted in phase B and three cells
have faulted in phase C. Without neutral-shift, one functional cell would be bypassed in
phase B, and three functional cells would be bypassed in phase A. Only 40% of the original
cells would remain in use, and only 40% of the original voltage would be available. However,

Table of Contents

Related product manuals