4. Mount earth wire in bottom of terminal box.
① Connect electrode cable
② Connect coil cable - keep separate from electrode cable
③ Connect power supply
④ Connect output cable
⑤ Connect PE (ground) wire
5. Mount connection plate in terminal box.
① Electrode cable
② Coil cable
③ Power supply
④ Output cable
6. Fit
coil, electrode, supply and output cables through cable glands and connect to connection
plate as shown in Electrical connection (Page 38).
7. Fix connection plate with the two diagonally opposite screws.
8. Tighten cable glands to obtain optimum sealing.
CAUTION
Coil cable shield
When remote mounted, power supply PE wire must be connected to PE terminal ( ).
Coil cable shield must be connected to SHIELD terminal.
Installing/Mounting
4.4 Remote installation
SITRANS FM MAG 5000/6000 IP67
Operating Instructions, 12/2019, A5E02338368-AD 29