Commissioning
6
In this chapter it is described how to commission the device via the local user interface (LUI).
The display is described in details in section
Local user interface (Page 42).
Furthermore, the following functions are described in details:
Changing password (Page 44)
Changing basic settings (Page 44)
Changing operator menu setup (Page 47)
Changing language (Page 48)
Detailed diagrams concerning the specific menu are shown in appendix menu diagrams.
For factory settings, see Factory settings (Page 95).
6.1 MAG 5000/6000 Blind
Note
Does not have a display. All factory settings will be uploaded from the SENSORPROM
®
unit
after power-up.
For sensor dependent factory settings, see Transmitter factory settings (Page 95).
Changing settings
If
other settings are required, a standard transmitter with display and similar power supply can
be used.
1. Unscrew and remove MAG 5000/6000 Blind.
2. Mount standard MAG 5000/6000 transmitter.
3. Change required settings via display and keypad.
All changed data will be stored in SENSORPROM
®
memory unit.
4. Remove standard transmitter and remount Blind transmitter.
5. Fasten screws holding transmitter.
New settings stored in SENSORPROM
®
memory unit will be uploaded in blind transmitter.
SITRANS FM MAG 5000/6000 IP67
Operating Instructions, 12/2019, A5E02338368-AD 41