Parameter Description
Low flow cut-off Setting of a percentage of selected Q
max
.
This filters noise in installation reducing
fluctuations in display and all outputs.
Empty pipe cut-off When set to "On" the alarm will indicate when sensor is running empty. All read‐
ings, display and outputs, will indicate zero.
Velocity unit Setting of velocity unit per time unit
Error level Selecting error level at which flowmeter will detect an error.
Note
Totalizer 2 is not visible when batch is selected as digital output.
Note
Q
max
2 is visible only when chosen as digital input.
Change basic settings as follows:
1.
Press top up key
for 2 sec.
2.
Enter password.
3. Use forward key
to reach basic settings menu.
4.
Press lock/unlock key
to unlock settings.
5.
Use forward key
or backward key to reach relevant menu.
6.
Press lock/unlock key
to unlock settings.
7.
Use select key
and change key to change settings.
8.
Press lock/unlock key
to confirm new settings.
Commissioning
6.5 Changing basic settings
SITRANS FM MAG 5000/6000 IP67
Operating Instructions, 12/2019, A5E02338368-AD 45