Error
No.
Error text
Remedy text
Comment Output
status
Input
status
42
P42 - Current output
Check cables
Current loop is disconnected or the loop resistance is
too big
Active
Active
43
P43 - Internal error
Switch off and on
Too many errors occurred at the same time.
Some errors are not detected correctly
Active
Active
44
P44 - CT SENSORPROM®
Replace
SENSORPROM
®
unit has been used as CT version
Active
Active
49
P49 - Protection violation
Switch off and on
Internal protection of the device has been violated. Active
60
F60 - CAN comm. error
Transmitter/AOM
CAN bus communication error. An add-on module,
the display module or the transmitter is defective
Zero
Inactive
61
F61 - SENSORPROM® error
Replace
It is not possible to rely on the data in SENSOR‐
PROM
®
unit anymore
Active
Active
62
F62 - SENSORPROM® ID
Replace
The SENSORPROM
®
unit ID does not comply with
the product ID.
The SENSORPROM
®
unit is from another type of
product SITRANS F C, SITRANS F US etc.
Zero
Inactive
63
F63 - SENSORPROM®
Replace
It is not possible to read from the SENSORPROM
®
unit anymore
Active
Active
70
F70 - Coil current
Check cables
Coil excitation has failed
Active
Active
71
F71 - Internal error
Replace transmitter
Internal conversion error in ASIC
Active
Active
Symptom Output sig‐
nals
Error code Cause Remedy
Empty display Minimum 1. No power supply Power supply
Check
MAG 5000/6000/6000 I for ben‐
ded pins on the connector
2. MAG 5000/6000/6000 I de‐
fective
Replace MAG 5000/6000/6000 I
Diagnostics and Troubleshooting