Parameter reference
SITRANS LR250 with mA/HART
122 Operating Instructions, 10/2019, A5E32220602-AG
Minimum mA limit (2.6.4.)
Prevents the mA output from dropping below this minimum level for a measurement value.
This does not restrict the Fail-safe or Manual settings.
Maximum mA limit (2.6.5.)
Prevents the mA output from rising above this maximum level for a measurement value. This
does not restrict the Fail-safe or Manual settings.
mA Output Value (2.6.6.)
Allows you to use a simulated value to test the functioning of the loop. You can enter 4 mA,
20 mA, or any other user-defined value within the range.
Range: 3.56 mA to 22.6 mA
Read Only unless Current Output Function (2.6.1.) is set to Manual.
Current Output Function (2.6.1.)
1. First set Current Output Function (2.6.1.) to Manual.
2. Enter the desired mA value in mA Output Value.
3. After completing the test, remember to reset Current Output Function (2.6.1.) to the
previous setting.
Via SIMATIC PDM:
Open the menu Device – Loop Test. For more detail, see Loop Test (Page 85).
Linearization (2.7.)
Volume (2.7.1.)
Carries out a volume conversion from a level value.