Parameter reference
SITRANS LR250 with mA/HART
136 Operating Instructions, 10/2019, A5E32220602-AG
TVT shaper (2.8.8.)
Note
The range is 100 to 100 bits. With 2 bits per dB this gives a range of 50 to 50 dB.
Shaper Mode (2.8.7.4.)
must be turned ON in order for TVT shaper points to be
transferred.
Adjusts the TVT (Time Varying Threshold) at a specified range (breakpoint on the TVT). This
allows you to reshape the TVT to avoid unwanted echoes. There are 40 breakpoints
arranged in 5 groups. (We recommend using SIMATIC PDM to access this feature.)
To use TVT shaper via SIMATIC PDM:
1. Go to Level Meter > Setup > Signal Processing > TVT setup > Shaper Mode and select
On.
2. Open the menu Device Echo Profile Utilities and click on TVT Shaper. For more detail
see
TVT shaper via SIMATIC PDM (Page 79).
To use TVT shaper via LUI (local user interface):
1. Go to Shaper Mode (2.8.7.4.) and select On.
2. Go to Breakpoint 1-9 (2.8.8.1.).
3. Open Shaper 1 and enter the TVT Offset value (between 50 and 50).
4. Go to the next Shaper point and repeat steps 3 and 4 until all desired breakpoint values
have been entered.
Breakpoint 1-9 (2.8.8.1.)
Values
Range: 50 to 50 dB
Default: 0 dB
Breakpoint 10-18 (2.8.8.2.)
Values
Range: 50 to 50 dB
Default: 0 dB
Breakpoint 19-27 (2.8.8.3.)
Values
Range: 50 to 50 dB
Default: 0 dB