Parameter reference
SITRANS LR250 with mA/HART
Operating Instructions, 10/2019, A5E32220602-AG
141
Time in Operation (4.2.2.)
Read only. The amount of time the device has been operating.
Remaining Lifetime (4.2.3.)
Read only. Lifetime (Expected) (4.2.1.) less Time in Operation (4.2.2.).
Activation of Reminders (4.2.4.)
Note
To modify this parameter via SIMAT
IC PDM it must be accessed via the pull-down menu
.
Allows you to enable a maintenance reminder.
ON - no reminders checked
ON - Reminder 1 (Maintenance Required) checked
ON - Reminders 1 and 2 checked
ON - Reminder 2 (Maintenance Demanded) checked
1. First set the values in Reminder 1 before Lifetime (Required) (4.2.5.)/ Reminder 2 before
Lifetime (Demanded) (4.2.6.).
2. Select the desired Activation of Reminders option.
Reminder 1 before Lifetime (Required) (4.2.5.)
If Remaining Lifetime (4.2.3.) is equal to or less than this value, the device generates a
Maintenance Required reminder.
Range: 0 to Lifetime (Expected) (4.2.1.)
1. Modify values as required.
2. Set Activation of Reminders (4.2.4.) to the desired option.
Reminder 2 before Lifetime (Demanded) (4.2.6.)
If Remaining Lifetime (4.2.3.) is equal to or less than this value, the device generates a
Maintenance Demanded reminder.
Range: 0 to Lifetime (Expected) (4.2.1.)
1. Modify values as required.
2. Set Activation of Reminders (4.2.4.) to the desired option.