Parameter reference
SITRANS LR250 with mA/HART
Operating Instructions, 10/2019, A5E32220602-AG
147
Service Interval (4.4.1.)
Note
The device always operates in years. Changing the units
affects only the parameter view of
the Service Interval parameters in SIMATIC PDM.
User-configurable recommended time between product inspections.
Values
Units
a)
: hours, days, years
Range: 0 to 20 years
Default: 1.0 year
a)
Units are selectable only via SIMATIC PDM.
Time Since Last Service (4.4.2.)
Time elapsed since last service. Can be reset to zero after performing a service.
To reset to zero:
In SIMATIC PDM, open the menu Device Maintenance, click on the Service Schedule
tab, and click on
Service Performed to restart the timer and clear any fault messages.
Via the handheld programmer, manually reset Time since Last Service (4.4.2.) to zero.
Time Until Next Service (4.4.3.)
Read only. Service Interval (4.4.1.) less Time Since Last Service (4.4.2.).