Parameter reference
SITRANS LR250 with mA/HART
Operating Instructions, 10/2019, A5E32220602-AG
151
Time Since Last Calibration (4.5.2.)
Time elapsed since last calibration. Can be reset to zero after performing a calibration.
To reset to zero:
● In SIMATIC PDM, open the menu Device – Maintenance, click on the Calibration
Schedule tab, and click on Calibration Performed to restart the timer and clear any fault
messages.
● Via the handheld programmer, manually reset Time Since Last Calibration (4.5.2.) to
zero.
Time Until Next Calibration (4.5.3.)
Read only. Calibration Interval (4.5.1.) less Time Since Last Calibration (4.5.2.).
Activation of Reminders (4.5.4.)
Note
To modify this parameter via SIMATIC PDM it must be accessed via the pull
-down menu
– Maintenance.
Allows you to enable a maintenance reminder.
ON - no reminders checked
ON - Reminder 1 (Maintenance Required) checked
ON - Reminders 1 and 2 checked
ON—Reminder 2 (Maintenance Demanded) checked
1. First set the values in Reminder 1 before Calibration (Required) (4.5.5.)/Reminder 2
before Calibration (Demanded) (4.5.6.).
2. Select the desired Activation of Reminders option.
Reminder 1 before Calibration (Required) (4.5.5.)
If Time Until Next Calibration (4.5.3.) is equal to or less than this value, the device generates
a
Maintenance Required reminder.
Range: 0 to Calibration Interval (4.5.1.)
1. Modify values as required.
2. Set Activation of Reminders (4.5.4.) to the desired option.