Remote operation
7.2 Operating via AMS Device Manager
SITRANS LR250 with mA/HART
96 Operating Instructions, 10/2019, A5E32220602-AG
5. If a vessel shape with parabolic ends has been selected, set dimensions A and L.
6. Click on Apply.
Step 5 – Summary
Check parameter settings, and click on Cancel to abort, or Apply to transfer values to the
device.
Linearization
You can use the linearization feature to define a more complex vessel shape and enter up to
32 level breakpoints where the corresponding volume is known. The values corresponding to
100% and 0% levels must be entered. The breakpoints can be ordered from top to bottom,
or the reverse.
Using linearization via the Quick Start wizard
Navigate to Configure/Setup > Wizard > Quick Start.
In Step 1 – Identification, make any desired modifications and click on Apply.
In Step 2 – Application, select a level application and liquid as a material.
In Step 3 – Vessel Shape, choose the vessel shape option Linearization Table.
In Step 4 – Ranges, enter a value for maximum volume.