Annunciations 7SA513 for LSA (DIN 19244 and according IEC 60870-5-103)
²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²
FNo. - Function number of annunciation
Op/Ft - Operation/Fault annunciation
C/CG: Coming/Coming and Going annunciation
V : Annunciation with Value
M : Measurand
LSA No.- Number of annunciation for former LSA (DIN 19244)
according to IEC 60870-5-103:
CA - Compatible Annunciation
GI - Annunciation for General Interrogation
BT - Binary Trace for fault recordings
Typ - Function type (p: according to the configured "Function type")
Inf - Information number
¿©©©©§©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©§©©©©©§©©©§©©©©©©©©©©©©©©©©¤
Ann.LSAIEC 60870-5-103
FNo. Meaning OpFtNo.CAGIBTTypInf
¨©©©©ª©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©ª©©ª©©ª©©©ª©©ª©©ª©©ª©©©ª©©©
11>User defined annunciation 1 CG 24CAGIBT p 27
12>User defined annunciation 2 CG 25CAGIBT p 28
13>User defined annunciation 3 CG 26CAGIBT p 29
14>User defined annunciation 4 CG 27CAGIBT p 30
15>Testing via system-interface 135 53
16>Block. of monitoring dir. via sys.-int 135 54
51Device operative / healthy CG 1 GI 135 81
52Any protection operative CG CAGI p 18
55Re-start of processor system C 8CAp4
56Initial start of processor system C 14CAp5
59Real time response to LSA C 6
60LED Reset C 13CAp19
61Logging and measuring functions blockedCG CAGI p 20
62Test mode CG CAGI p 21
63PC operation via system interface CG GI 135 83
95Parameters are being set CG 11CAGI p 22
96Parameter set A is active CG 40CAGI p 23
97Parameter set B is active CG 41CAGI p 24
98Parameter set C is active CG 42CAGI p 25
99Parameter set D is active CG 43CAGI p 26
110Annunciations lost (buffer overflow) C 9 135130
112Annunciations for LSA lost C 10 135131
113Fault tag lost BT135136
140General internal failure of device CG CAGI p 47
141Failure of internal 24 VDC power supplyCG 96 GI 135161
143Failure of internal 15 VDC power supplyCG 97 GI 135163
144Failure of internal 5 VDC power supply CG 98 GI 135164
145Failure of internal 0 VDC power supply CG 99 GI 135165
154Supervision trip circuit CG 100CAGI p 36
160Common alarm CG CAGI p 46
161Measured value supervision of currents CG CAGI p 32
162Failure: Current summation supervision CG 104 GI 135182
163Failure: Current symmetry supervision CG 107 GI 135183
164Measured value supervision of voltages CG CAGI p 33
165Failure: Voltage sum superv. (ph-e) CG 105 GI 135184
166Failure: Voltage sum superv. (ph-ph) CG 106 GI 135185
167Failure: Voltage symmetry supervision CG 108 GI 135186
168Failure: Measuring voltages absent CG 109 GI 135187
169Fuse failure monitor operated (>10s) CG 110 GI 135188
171Failure: Phase sequence supervision CG 111CAGI p 35
204Fault recording initiated via bin.input BT135204
¥©©©©¦©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©¦©©¦©©¦©©©¦©©¦©©¦©©¦©©©¦©©©¾