Ann.LSAIEC 60870-5-103
FNo. Meaning OpFtNo.CAGIBTTypInf
¨©©©©ª©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©ª©©ª©©ª©©©ª©©ª©©ª©©ª©©©ª©©©
205Fault recording initiated via keyboard BT135205
206Fault recording initiated via PC interf BT135206
301Fault in the power system CG 2 135231
302Flt. event w. consecutive no. C 135232
361>U Line side VT MCB tripped CG 20CAGI p 38
362>U2 Busbar side VT MCB tripped CG 19 GI 150 12
501General fault detection of device CG CAGIBT p 84
502General drop-off of device C 152 150152
503General device fault detection: Ph. L1 CG CAGIBT p 64
504General device fault detection: Ph. L2 CG CAGIBT p 65
505General device fault detection: Ph. L3 CG CAGIBT p 66
506General device fault detection: Ph. N CG CAGIBT p 67
507General device trip: Phase L1 C CA BT p 69
508General device trip: Phase L2 C CA BT p 70
509General device trip: Phase L3 C CA BT p 71
511General trip of device C CA BT p 68
516General trip for fault in forward dir. CG242 150166
517General trip for fault in reverse dir. CG243 150167
521Interrupted current: Phase L1(I/In) V250 150171
522Interrupted current: Phase L2(I/In) V251 150172
523Interrupted current: Phase L3(I/In) V252 150173
561Circuit breaker manually closed (pulse)C 18 150211
562CB close command for manual closing C 249 150212
601Current in phase IL1 [%] = M CA 134128
602Current in phase IL2 [%] = M CA 134128
603Current in phase IL3 [%] = M CA 134128
621UL1E [%]= M CA 134128
622UL2E [%]= M CA 134128
623UL3E [%]= M CA 134128
624UL12 [%] = M 134128
625UL23 [%] = M 134128
626UL31 [%] = M 134128
641Active power Pa [%] = M CA 134128
642Reactive power Pr [%] = M CA 134128
644Frequency f [%] = M CA 134128
1114Fault resistance, Ohm prim. V 151 14
1115Fault reactance, Ohm prim. V CAp73
1117Fault resistance, Ohm sec. V201 151 17
1118Fault reactance, Ohm sec. V202 151 18
1119Distance to fault in km V203 151 19
1120Distance to fault in % V204 151 20
1174Circuit breaker test in progress CG 21 GI 151 74
1181Circuit breaker test: General trip C 125 151 81
1316>Carrier reception for direct. E/F compCG 68 GI 166 16
1317>Carrier reception for dir. E/F faulty CG 67 GI 166 17
1331Earth fault protection is switched off CG 71 GI 166 31
1332Earth fault protection is blocked CG 64 GI 166 32
1333Earth fault protection is active CG GI 166 33
1334Earth fault prot. direct.stage blocked CG GI 166 34
1341Earth fault detection 75% Ie picked up CG208 BT166 41
1342Earth fault detection non-direct. Ie CG209 166 42
1343Earth fault detection directional Ie CG207 166 43
1361Trip by earth fault protection C 247 166 61
1362Earth fault protection: Trip 1pole L1 C 210 166 62
1363Earth fault protection: Trip 1pole L2 C 211 166 63
1364Earth fault protection: Trip 1pole L3 C 212 166 64
1365Earth fault protection: Trip 3pole C 213 166 65