Set the voltage to a multiple of the threshold value. Siemens recommends setting the Threshold parameter
to 1.00 in order to obtain a simple relation. You can change the threshold value afterwards if you want to
shift the characteristic curve.
Set the time value in seconds. The characteristic curve is shifted via the Time dial parameter.
Set the number of value pairs to be used with DIGSI. You can define a maximum of 30 value pairs.
NOTE
The value pairs must be entered in continuous order.
Settings
Addr. Parameter C Setting Options Default Setting
General
_:1 User curve #:Mode
•
off
•
on
•
test
off
_:2 User curve #:Operate &
flt.rec. blocked
•
no
•
yes
no
_:3 User curve #:Threshold 0.80 p.u. to 3.00 p.u. 1.10 p.u.
_:101 User curve #:Time dial 0.05 to 15.00 1.00
Information List
No.
Information Data Class
(Type)
Type
User curve #
_:81 User curve #:>Block stage SPS I
_:54 User curve #:Inactive SPS O
_:52 User curve #:Behavior ENS O
_:53 User curve #:Health ENS O
_:55 User curve #:Pickup ACD O
_:56 User curve #:Operate delay expired ACT O
_:57 User curve #:Operate ACT O
_:301 User curve #:Down integr. running SPS O
7.6.5.3
7.6.5.4
Capacitor Bank Protection
7.6 Peak Overvoltage Protection for Capacitors
SIPROTEC 5, Overcurrent Protection, Manual 1031
C53000-G5040-C017-8, Edition 07.2017