Information List
No. Information Data Class
(Type)
Type
General
_:2311:300 General:I diff. WYE O
_:2311:301 General:I restr. WYE O
_:2311:311 General:I diff. operate phA MV O
_:2311:312 General:I diff. operate phB MV O
_:2311:313 General:I diff. operate phC MV O
_:2311:314 General:I restr. operate phA MV O
_:2311:315 General:I restr. operate phB MV O
_:2311:316 General:I restr. operate phC MV O
_:2311:317 General:Adapt. adjustm. inact. SPS O
I-DIFF
_:11041:81 I-DIFF:>Block stage SPS I
_:11041:54 I-DIFF:Inactive SPS O
_:11041:52 I-DIFF:Behavior ENS O
_:11041:53 I-DIFF:Health ENS O
_:11041:55 I-DIFF:Pickup ACD O
_:11041:56 I-DIFF:Operate delay expired ACT O
_:11041:57 I-DIFF:Operate ACT O
_:11041:301 I-DIFF:Slope 1 MV O
_:11041:302 I-DIFF:Incr. of char. (Start) SPS O
_:11041:303 I-DIFF:Increase of char. (DC) SPS O
_:11041:304 I-DIFF:Blocked by inrush SPS O
_:11041:305 I-DIFF:Blocked by 2.Harmon. ACT O
_:11041:306 I-DIFF:Crossblock by 2.Harm. SPS O
_:11041:312 I-DIFF:Blocked by ext. fault ACT O
_:11041:313 I-DIFF:Crossbl. by ext. fault SPS O
_:11041:316 I-DIFF:CWA int. fault detected SPS O
I-DIFF fast
_:11071:81 I-DIFF fast:>Block stage SPS I
_:11071:54 I-DIFF fast:Inactive SPS O
_:11071:52 I-DIFF fast:Behavior ENS O
_:11071:53 I-DIFF fast:Health ENS O
_:11071:55 I-DIFF fast:Pickup ACD O
_:11071:57 I-DIFF fast:Operate ACT O
_:11071:56 I-DIFF fast:Operate delay expired ACT O
I-DIFF unrestr
_:18002:81 I-DIFF unrestr:>Block stage SPS I
_:18002:54 I-DIFF unrestr:Inactive SPS O
_:18002:52 I-DIFF unrestr:Behavior ENS O
_:18002:53 I-DIFF unrestr:Health ENS O
_:18002:55 I-DIFF unrestr:Pickup ACD O
_:18002:57 I-DIFF unrestr:Operate ACT O
_:18002:56 I-DIFF unrestr:Operate delay expired ACT O
7.8.6
Capacitor Bank Protection
7.8 Differential Protection for Capacitor Banks
1068 SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017