Addr. Parameter C Setting Options Default Setting
_:16351:109 90V V.contr.gc:Control
model
•
direct w. normal secur.
•
SBO w. normal secur.
•
direct w. enh. security
•
SBO w. enh. security
SBO w. enh.
security
_:16351:110 90V V.contr.gc:SBO
time-out
0.01 s to 1800.00 s 30.00 s
_:16351:111 90V V.contr.gc:Feedback
monitoring time
0.01 s to 1800.00 s 10.00 s
Voltage Control
_:16351:164 90V V.contr.gc:Number
of target voltage
•
1
•
2
•
3
•
4
1
_:16351:112 90V V.contr.gc:Target
voltage 1 w1
10.000 V to 340.000 V 110.000 V
_:16351:165 90V V.contr.gc:Target
voltage 2 w1
10.000 V to 340.000 V 110.000 V
_:16351:166 90V V.contr.gc:Target
voltage 3 w1
10.000 V to 340.000 V 110.000 V
_:16351:167 90V V.contr.gc:Target
voltage 4 w1
10.000 V to 340.000 V 110.000 V
_:16351:146 90V V.contr.gc:Target
voltage 1 w2
10.000 V to 340.000 V 110.000 V
_:16351:168 90V V.contr.gc:Target
voltage 2 w2
10.000 V to 340.000 V 110.000 V
_:16351:169 90V V.contr.gc:Target
voltage 3 w2
10.000 V to 340.000 V 110.000 V
_:16351:170 90V V.contr.gc:Target
voltage 4 w2
10.000 V to 340.000 V 110.000 V
_:16351:113 90V V.contr.gc:Band-
width
0.2 % to 10.0 % 1.0 %
_:16351:114 90V V.contr.gc:T1 char-
acteristic
•
Linear
•
Inverse
Linear
_:16351:115 90V V.contr.gc:T1 delay 5 s to 600 s 40 s
_:16351:116 90V V.contr.gc:T1
Inverse Min
5 s to 100 s 5 s
_:16351:117 90V V.contr.gc:T2 delay 0 s to 100 s 5 s
_:16351:118 90V V.contr.gc:Fast step
up
•
off
•
on
off
_:16351:119 90V V.contr.gc:Fast step
up limit
-50.0 % to 0.0 % -6.0 %
_:16351:120 90V V.contr.gc:Fast step
up T delay
0.0 s to 10.0 s 2.0 s
_:16351:121 90V V.contr.gc:Fast step
down
•
off
•
on
on
_:16351:122 90V V.contr.gc:Fast step
down limit
0.0 % to 50.0 % 6.0 %
_:16351:123 90V V.contr.gc:Fast step
down T delay
0.0 s to 10.0 s 0.0 s
_:16351:124 90V V.contr.gc:Function
monitoring
0 min to 120 min 15 min
Control Functions
8.9 Voltage Controller
SIPROTEC 5, Overcurrent Protection, Manual 1229
C53000-G5040-C017-8, Edition 07.2017