These modules are then freely assignable to ports E, F, N, or P of the device, see Figure 10-10. You can view
the selected port in the (_:10621:104) Port. This parameter is automatically managed by DIGSI and
cannot be changed.
[sccommod-140213-01.tif, 1, en_US]
Figure 10-10 Placement of Communication Modules
i
i
NOTE
Port M of the CB202 plug-in module assembly is used to accommodate measuring-transducer modules and
cannot be used for the installation of communication modules.
Addressing
You must configure the respective Ethernet address (IP address, subnet mask, etc.) for each communication
module in DIGSI. This is done in the DIGSI General settings properties dialog of the communication module in
item Ethernet addresses and so forms the IP address for the respective PMU.
[scethern-210415, 1, en_US]
Figure 10-11 Ethernet Address Configuration
In the DIGSI properties dialog for channel 1, select the synchrophasor protocol, see the following figure.
Measured Values, Energy Values, and Supervision of the Primary System
10.9 Phasor Measurement Unit (PMU)
SIPROTEC 5, Overcurrent Protection, Manual 1333
C53000-G5040-C017-8, Edition 07.2017