Siemens 7SJ82 - Directional 3 I0 Stage with Cos Φ or sin Φ Measurement

Siemens 7SJ82
1638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Direction-calculation angle error
94
≤ 1° at 3I0 > 5 mA, V0 = 0.6 V
≤ 2° at 3I0 ≤ 5 mA, V0 = 0.6 V
Directional 3I0 Stage with Cos φ or Sin φ Measurement
Setting Values
Direction method of measurement cos φ
sin φ
Threshold value
3I0>
Minimum direc-
tional 3I0> for
direction determi-
nation
Protection-class
current trans-
formers
For I
ph-rated
=
1 A
0.030 A to 35.000 A Increments of 0.001 A
For I
ph-rated
=
5 A
0.15 A to 175.00 A Increments of 0.01 A
For I
N
transformer
type sensitive
and I
N-rated
= 1 A
For I
ph-rated
=
1 A
0.001 A to 35.000 A Increments of 0.001 A
For I
ph-rated
=
5 A
0.001 A to 175.000 A Increments of 0.001 A
For I
N
transformer
type sensitive
and I
N-rated
= 5 A
For I
ph-rated
=
1 A
0.005 A to 35.000 A Increments of 0.001 A
For I
ph-rated
=
5 A
0.005 A to 175.000 A Increments of 0.001 A
Threshold value V0> 0.300 V to 200.000 V Increments of 0.001 V
Time delay of the direction determination 0.00 s to 60.00 s Increments of 0.01 s
α1 constraint of the direction range
α2 constraint of the direction range
1° to 15° Increments of 1°
Angle correction φ -45° to 45° Increments of 1°
Tripping delay 0.00 s to 60.00 s Increments of 0.01 s
Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter
Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent/overvoltage and of 105 % for
undercurrent/undervoltage functionality.
Minimum absolute dropout differential
Protection-class current transformer 15 mA sec. (I
rated
= 1 A) or
75 mA sec. (I
rated
= 5 A)
Instrument current transformer 0.5 mA sec. (I
rated
= 1 A) or
2.5 mA sec. (I
rated
= 5 A)
Voltage transformer 150 mV sec.
Times
Operate time with time delay = 0 ms
Approx. 32 ms + OOT
95
at 50 Hz
Approx. 29 ms + OOT at 60 Hz
Extension of the operate time during operation with
transformer inrush-current detection
Approx. 10 ms
12.18.2
94
Not applicable to 12.18.4 Directional 3I0 Stage with φ(V0,3I0) Measurement
95
OOT (Output Operating Time): additional delay of the output medium used, see Chapter 12.1.4 Relay Outputs
Technical Data
12.18 Sensitive Ground-Fault Detection
SIPROTEC 5, Overcurrent Protection, Manual 1477
C53000-G5040-C017-8, Edition 07.2017