Siemens 7SJ82 - Directional Transient Ground-Fault Stage; Directional 3 I0 Stage with Φ(V0,3 I0) Measurement

Siemens 7SJ82
1638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Dropout time Approx. 32 ms + OOT at 50 Hz
Approx. 27 ms + OOT at 60 Hz
Directional Transient Ground-Fault Stage
Setting Values
Threshold
value 3I0>
Protection-class
current transformers
For I
ph-rated
=
1 A
0.000 A to 35.000 A Increments of 0.001 A
For I
ph-rated
=
5 A
0.00 A to 175.00 A Increments of 0.01 A
Sensitive current
transformer for I
N
I
N-rated
= 1 A 0.000 A to 1.600 A Increments of 0.001 A
I
N-rated
= 5 A 0.000 A to 8.000 A Increments of 0.001 A
Threshold value V0> 0.300 V to 200.000 V Increments of 0.001 V
Maximum operational V0 0.300 V to 200.000 V Increments of 0.001 V
Dropout delay 0.00 s to 60.00 s Increments of 0.01 s
Tripping delay 0.00 s to 60.00 s Increments of 0.01 s
Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter
Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent/overvoltage and of 105 % for
undercurrent/undervoltage functionality.
Minimum absolute dropout differential
Protection-class current transformer 15 mA sec. (I
rated
= 1 A) or
75 mA sec. (I
rated
= 5 A)
Instrument current transformer 0.5 mA sec. (I
rated
= 1 A) or
2.5 mA sec. (I
rated
= 5 A)
Voltage transformer 150 mV sec.
Times
Operate time with time delay = 0 ms
Approx. 115 ms + OOT
96
at 50 Hz
Approx. 112 ms + OOT at 60 Hz
Dropout time Approx. 20 ms + OOT at 50 Hz
Approx. 15 ms + OOT at 60 Hz
Directional 3I0 Stage with φ(V0,3I0) Measurement
Setting Values
Threshold value
3I0>
Protection-class
current transformers
For I
ph-rated
= 1 A 0.030 A to 35.000 A Increments of 0.001 A
For I
ph-rated
= 5 A 0.15 A to 175.00 A Increments of 0.01 A
For I
N
transformer type
sensitive
and I
N-rated
= 1 A
For I
ph-rated
= 1 A 0.001 A to 35.000 A Increments of 0.001 A
For I
ph-rated
= 5 A 0.001 A to 175.000 A Increments of 0.001 A
12.18.3
12.18.4
96
OOT (Output Operating Time): additional delay of the output medium used, see chapter 12.1.4 Relay Outputs
Technical Data
12.18 Sensitive Ground-Fault Detection
1478 SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017