Directional Stage with Phasor Measurement of a Harmonic
Setting Values
Min. 3I0> of the
selected
harmonic phasor
Protection-class
current transformers
For I
ph-rated
= 1 A 0.030 A to 35.000 A Increments of 0.001 A
For I
ph-rated
= 5 A 0.15 A to 175.00 A Increments of 0.01 A
For I
N
transformer type
sensitive
and I
N-rated
= 1 A
For I
ph-rated
= 1 A 0.001 A to 35.000 A Increments of 0.001 A
For I
ph-rated
= 5 A 0.001 A to 175.000 A Increments of 0.001 A
For I
N
transformer type
sensitive
and I
N-rated
= 5 A
For I
ph-rated
= 1 A 0.005 A to 35.000 A Increments of 0.001 A
For I
ph-rated
= 5 A 0.005 A to 175.000 A Increments of 0.001 A
Dropout ratio of the direction determination in terms of the
zero-sequence harmonic current
0.10 to 0.95 Increments of 0.01
Threshold value V0> 0.300 V to 200.000 V Increments of 0.001 V
Time delay of the direction determination 0.00 s to 60.00 s Increments of 0.01 s
Extension of the direction result 0.00 s to 60.00 s Increments of 0.01 s
Forward range +/- 0° to 90° Increments of 1°
Tripping delay 0.00 s to 60.00 s Increments of 0.01 s
Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter
Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent/overvoltage and of 105 % for
undercurrent/undervoltage functionality.
Minimum absolute dropout differential
Protection-class current transformer 15 mA sec. (I
rated
= 1 A) or
75 mA sec. (I
rated
= 5 A)
Instrument current transformer 0.5 mA sec. (I
rated
= 1 A) or
2.5 mA sec. (I
rated
= 5 A)
Voltage transformer 150 mV sec.
Times
Operate time with time delay = 0 ms
Approx. 70 ms + OOT
99
at 50 Hz
Approx. 60 ms + OOT at 60 Hz
Dropout time Approx. 30 ms + OOT at 50 Hz
Approx. 20 ms + OOT at 60 Hz
12.18.6
99
OOT (Output Operating Time): additional delay of the output medium used, see chapter 12.1.4 Relay Outputs
Technical Data
12.18 Sensitive Ground-Fault Detection
SIPROTEC 5, Overcurrent Protection, Manual 1481
C53000-G5040-C017-8, Edition 07.2017