Addr. Parameter C Setting Options Default Setting
_:8131:36 Definite-T 1:Stage
blocked
no
yes
no
_:8131:14 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:8131:20 Definite-T 1:Operate
delay
0.00 s to 60.00 s 0.30 s
Dyn.set: AR cycle 2
_:8131:30 Definite-T 1:Effected by
AR cycle 2
no
yes
no
_:8131:37 Definite-T 1:Stage
blocked
no
yes
no
_:8131:15 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:8131:21 Definite-T 1:Operate
delay
0.00 s to 60.00 s 0.30 s
Dyn.set: AR cycle 3
_:8131:31 Definite-T 1:Effected by
AR cycle 3
no
yes
no
_:8131:38 Definite-T 1:Stage
blocked
no
yes
no
_:8131:16 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:8131:22 Definite-T 1:Operate
delay
0.00 s to 60.00 s 0.30 s
Dyn.s: AR cycle>3
_:8131:32 Definite-T 1:Effected by
AR cycle gr. 3
no
yes
no
_:8131:39 Definite-T 1:Stage
blocked
no
yes
no
_:8131:17 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:8131:23 Definite-T 1:Operate
delay
0.00 s to 60.00 s 0.30 s
Protection and Automation Functions
6.6 Directional Overcurrent Protection, Phases
SIPROTEC 5, Overcurrent Protection, Manual 417
C53000-G5040-C017-8, Edition 07.2017

Table of Contents

Related product manuals